The Trident Giant 40M is a high-performance, industrial-grade air-to-water heat pump designed specifically for the heating, cooling and domestic hot water needs of buildings with high heat demand. It is a reliable choice for apartment buildings, industrial and commercial facilities, public institutions and large-area properties.
High performance, engineered for industrial applications
The Trident Giant 40M operates across an exceptionally wide output range, allowing it to adapt efficiently to changing heat demand. The system provides stable heating output even at low outdoor temperatures, while in cooling mode its high capacity maintains a comfortable indoor temperature.
The unit's design allows for:
-
serving larger heating systems,
-
efficiently operating multiple heating circuits and systems with large water volumes,
-
continuous operation under industrial and commercial workloads.
Energy-efficient inverter technology
The Giant 40M employs inverter + EVI technology that matches operation to the actual load. As a result:
-
energy consumption is reduced,
-
part-load efficiency improves,
-
smoother and more stable operation is achieved even in large systems.
The system runs on R290 refrigerant, offering an environmentally friendly solution with high efficiency and low environmental impact.
Industrial-grade components, long service life
The Trident Giant 40M uses premium-quality components designed for industrial applications:
-
high-performance inverter compressor,
-
titanium shell-and-tube heat exchanger,
-
high-airflow fan.
This construction ensures reliable operation over the long term, even under intensive use.
Versatile system integration
With appropriate system design, the Trident Giant 40M integrates seamlessly with:
-
underfloor heating and radiator systems,
-
fan coil based cooling systems,
-
solutions with buffer tanks and large DHW storage,
-
cascaded, multi-unit systems.
Who is it recommended for?
The Trident Giant 40M is an ideal choice for those who:
-
are looking for a heat pump solution for a building with high heat demand,
-
are planning for an industrial or commercial environment,
-
want a stable, energy-efficient and scalable system for the long term.
The Giant 40M is recommended for projects where performance, reliability and dependable operation are the top priorities.
Key features
| Heat pump energy efficiency class - W35°C / W55°C | A+++ / A+++ |
|---|---|
| SCOP - 35°C / 55°C | 4.86 / 3.71 |
| SEER - 18°C / 7°C | 5.82 / 3.54 |
| Annual energy consumption - heating (35°C/55°C) | 12166 kWh / 15641 kWh |
| Rated heat output (Prated) (35°C/55°C) | 38.6 kW / 38.1 kW |
| Maximum heat output (35°C/55°C) | 38.62 kW / 37.54 kW |
Heat outputs
| Heating capacity A7/W35 (min/max) | 12.70 kW / 38.60 kW |
|---|---|
| Heating capacity A2/W35 (min/max) | 11.0 kW / 35.5 kW |
| Heating capacity A-7/W35 (min/max) | 8.40 kW / 35.20 kW |
| Heating capacity (A7/W35) | 38.62 kW |
| Electrical power input (A7/W35) | 12.30 kW |
| COP (A7/W35) | 3.15 |
| Heating capacity (A7/W55) | 37.54 kW |
| Electrical power input (A7/W55) | 13.95 kW |
| COP (A7/W55) | 2.69 |
| Heating capacity (A2/W35) | 35.51 kW |
| Electrical power input (A2/W35) | 11.05 kW |
| COP (A2/W35) | 3.21 |
| Heating capacity (A2/W55) | 31.21 kW |
| Electrical power input (A2/W55) | 12.80 kW |
| COP (A2/W55) | 2.44 |
| Heating capacity (A-7/W35) | 25.20 kW |
| Electrical power input (A-7/W35) | 9.02 kW |
| COP (A-7/W35) | 2.81 |
| Heating capacity (A-7/W55) | 21.32 kW |
| Electrical power input (A-7/W55) | 12.37 kW |
| COP (A-7/W55) | 1.72 |
| Cooling capacity (A35/W18) | 34.21 kW |
| Electrical power input (A35/W18) | 9.14 kW |
| EER (A35/W18) | 3.76 |
| Cooling capacity (A35/W7) | 25.14 kW |
| Electrical power input (A35/W7) | 9.41 kW |
| EER (A35/W7) | 2.59 |
At operating points with an outdoor temperature of 2 °C or below (A2, A-7, A-15), the heating data is given without the defrost cycle included.
Performance data
| Refrigerant | R290 |
|---|---|
| Refrigerant charge | 4.2 kg |
| Compressor type | Twin rotary |
| Compressor manufacturer | Copeland compressor |
| Compressor oil | PAG |
| Number of refrigerant circuits | 1 |
Electrical data
| Rated voltage of outdoor unit | 400 V |
|---|---|
| Recommended fuse for outdoor unit | 3 x B 30 A |
Hydraulic data
| Heat exchanger type | Plate heat exchanger |
|---|---|
| Heat exchanger manufacturer | Danfoss |
| Water-side pipe connection | G2" male thread |
| Nominal flow rate | 6.9 m³/h |
| Min. / max. flow rate | 4.7 / 8.9 m³/h |
Heat source data
| Number of fans | 1 db |
|---|---|
| Fan air flow rate | 13500 m³/h |
Operating limits
| Outdoor temperature operating range | −25 / 43 °C |
|---|---|
| Heating water temperature (min/max) | 25 / 75 °C |
| Cooling water temperature (min/max) | 7 / 20 °C |
| Min. / max. operating pressure | 0.8 / 3 bar |
Weight data
| Weight | 350 kg |
|---|
Dimensions
| Width | 1.17 m |
|---|---|
| Depth | 0.97 m |
| Height | 1.62 m |
Noise level
| Sound power level (EN 12102) | 62 dB(A) |
|---|---|
| Max. sound power level at operating limits | 81 dB(A) |
| Max. sound power level in reduced night mode | 72 dB(A) |