Trident Giant 30M
Indoor unit
Outdoor unit
Trident Giant 30M
SKU: TT-AW-0030-CB-01-33-01
€13,130 excl. VAT
Maximum water temperature of 75 °C, very quiet operation, R290 refrigerant, 3+7 years extended warranty.
Key features
Questions about this product?
Get in touch with us.
Specifications
The Trident Giant 30M is a high-performance, inverter-driven air-to-water heat pump designed specifically for the heating, cooling and domestic hot water needs of residential and industrial buildings with higher heat demand. It offers a reliable and energy-efficient solution for apartment buildings, industrial facilities, public institutions, office buildings and large-area properties.
Stable performance for large systems
The Trident Giant 30M operates across a wide output range, allowing it to adapt efficiently to changing heat demand. The system delivers reliable heating output even at low outdoor temperatures, while in cooling mode its high capacity keeps indoor spaces at a comfortable temperature.
Its design allows for:
-
serving heating systems with large water volumes,
-
operating several heating circuits simultaneously,
-
continuous operation in industrial and commercial environments.
Inverter technology with EVI support
The Giant 30M employs advanced inverter + EVI technology that matches operation to the actual load. Its benefits include:
-
lower energy consumption at part load,
-
smoother operation in large systems,
-
improved efficiency even at extreme outdoor temperatures.
The system runs on R290 refrigerant, offering an environmentally friendly solution with high efficiency and low environmental impact.
Industrial-grade components
The Trident Giant 30M uses premium components designed for industrial applications:
-
high-performance inverter compressor,
-
efficient water-side heat exchanger,
-
high-airflow fans.
This construction ensures a long service life and stable operation even under intensive use.
Flexible system integration
With appropriate system design, the Trident Giant 30M integrates seamlessly with:
-
underfloor heating and radiator systems,
-
fan coil based cooling solutions,
-
systems with buffer tanks and large DHW storage,
-
cascaded, multi-unit configurations.
Who is it recommended for?
The Trident Giant 30M is an ideal choice for those who:
-
are looking for a heat pump solution for a building with higher heat demand,
-
are planning for an industrial or commercial environment,
-
want a stable, energy-efficient and expandable system for the long term.
The Giant 30M is recommended for projects where performance, operational reliability and scalability are key.
Key features
| Heat pump energy efficiency class - W35°C / W55°C | A+++ / A+++ |
|---|---|
| SCOP - 35°C / 55°C | 5.10 / 3.83 |
| SEER - 18°C / 7°C | 5.51 / 3.72 |
| Annual energy consumption - heating (35°C/55°C) | 10129 kWh / 12950 kWh |
| Rated heat output (Prated) (35°C/55°C) | 29.1 kW / 29.3 kW |
| Maximum heat output (35°C/55°C) | 30.73 kW / 29.18 kW |
Heat outputs
| Heating capacity A7/W35 (min/max) | 8.33 kW / 30.73 kW |
|---|---|
| Heating capacity A2/W35 (min/max) | 12.14 kW / 27.51 kW |
| Heating capacity A-7/W35 (min/max) | 10.07 kW / 26.28 kW |
| Heating capacity (A7/W35) | 30.73 kW |
| Electrical power input (A7/W35) | 6.95 kW |
| COP (A7/W35) | 4.42 |
| Heating capacity (A7/W55) | 29.18 kW |
| Electrical power input (A7/W55) | 9.81 kW |
| COP (A7/W55) | 2.97 |
| Heating capacity (A2/W35) | 27.51 kW |
| Electrical power input (A2/W35) | 9.06 kW |
| COP (A2/W35) | 3.04 |
| Heating capacity (A2/W55) | 26.01 kW |
| Electrical power input (A2/W55) | 11.13 kW |
| COP (A2/W55) | 2.34 |
| Heating capacity (A-7/W35) | 26.28 kW |
| Electrical power input (A-7/W35) | 9.14 kW |
| COP (A-7/W35) | 2.87 |
| Heating capacity (A-7/W55) | 25.16 kW |
| Electrical power input (A-7/W55) | 12.10 kW |
| COP (A-7/W55) | 2.08 |
| Cooling capacity (A35/W18) | 30.65 kW |
| Electrical power input (A35/W18) | 8.89 kW |
| EER (A35/W18) | 3.67 |
| Cooling capacity (A35/W7) | 23.45 kW |
| Electrical power input (A35/W7) | 8.93 kW |
| EER (A35/W7) | 2.63 |
At operating points with an outdoor temperature of 2 °C or below (A2, A-7, A-15), the heating data is given without the defrost cycle included.
Performance data
| Refrigerant | R290 |
|---|---|
| Refrigerant charge | 2.7 kg |
| Compressor type | Twin rotary |
| Compressor manufacturer | Mitsubishi Electric |
| Compressor oil | PZ46M |
| Number of refrigerant circuits | 1 |
Electrical data
| Rated voltage of outdoor unit | 400 V |
|---|---|
| Recommended fuse for outdoor unit | 3 x B 25 A |
Hydraulic data
| Heat exchanger type | Plate heat exchanger |
|---|---|
| Heat exchanger manufacturer | Danfoss |
| Water-side pipe connection | G6/4" male thread |
| Nominal flow rate | 5.1 m³/h |
| Min. / max. flow rate | 2.9 / 6.6 m³/h |
Heat source data
| Number of fans | 2 db |
|---|---|
| Fan air flow rate | 11000 m³/h |
Operating limits
| Outdoor temperature operating range | −25 / 43 °C |
|---|---|
| Heating water temperature (min/max) | 25 / 75 °C |
| Cooling water temperature (min/max) | 7 / 20 °C |
| Min. / max. operating pressure | 0.8 / 3 bar |
Weight data
| Weight | 340 kg |
|---|
Dimensions
| Width | 1.54 m |
|---|---|
| Depth | 0.55 m |
| Height | 1.74 m |
Noise level
| Sound power level (EN 12102) | 55 dB(A) |
|---|---|
| Max. sound power level at operating limits | 74 dB(A) |
| Max. sound power level in reduced night mode | 67 dB(A) |
Have a technical question?